VTS 38 Voltage instrument transformers VTS 38 are single-phase transformers isolated with one pole. They are designed for the use in the high voltage systems. They are designed for measuring and protection ...

We measure high voltage for you

using instrument transformers for both outdoor and indoor applications, special transformers, sensors and power transformers


 

VTS 38
Insulation voltage 40.5 kV
Test voltage 95 kV
Test impulse voltage 200 kV
Nominal primary voltage 3000/√3 – 35000/√3 V
Nominal secondary voltage 100/√3, 110/√3, 120/√3 V
Nominal auxiliary voltage 100/3, 110/3, 120/3 V
Nominal frequency 50 Hz
Power 10, 30, 50, 75, 100, 150 VА
Accuracy class 0.2, 0.5, 1, 3Р, 6Р
Extreme power 500 VА
Weight 33 kg
Approval TCM 212/98-2963
drawing [ZIP, 93kB] in DXF format

Voltage instrument transformers VTS 38 are single-phase transformers isolated with one pole. They are designed for the use in the high voltage systems. They are designed for measuring and protection of high voltage distributing equipment for indoor design. The instruments can be equipped with high voltage fuse protecting the surrounding distributing system.

The values of secondary voltage are 100/√3, 110/√3, 120/√3, 100/3, 110/3, 120/3 V. The accuracy classes for measuring winding are 0.2, 0.5, 1, 3, for the securing winding are 3P and 6P. The transformers satisfy required accuracy class at intervals from 25% to 100% of rated load.

Transformers VTS 38 with fuse are provided with plastics extender, holder and fuse enclosure of type Bussmann (36OBGNA 3.15A). Extender with fuse can be dismounted.

Magnetic circuit of voltage transformers VTS 38 is made of oriented transformer strips in the shape of “C” of core.

All active parts of transformer are compound-insulated with epoxy-mixture. This material performs both the electrical insulating and the mechanical functions.

Transformers are fixed by the means of four screws M12 in the holes in the basic plate. The outlet of primary winding “A” is brought out by the means of bolt M10.

We recommend for contacting VTS 38 for the reason of spring mounting of the dynamic strengths and vibrationsto use leading wires of maximum cross section of 6 mm2 and cable sockets.

ATTENTION: The isolators must not be pre-stressed mechanically in the direction away from the body of transformer during the other way of contacting.

We recommend use terminal ends corresponding to the used cross-section of the conductor for attaching to the secondary outlets. The secondary terminal plate is provided with the cover with sealing screw. Inside, there is the set with jumpers and small screws for the possibility of earth connection and short circuiting of the wiring. (See“The Instructions for the mounting and operation”).

In cases where the substitution for the older types of transformers (various producers) is required, we supplytransformers VTS 38 with modified basic plates that have identical mounting spacing to spacing of the substituted types.

Voltage instrument transformers VTS 38 complied with all the tests according to ČSN EN 60044-2 and GOST1983-89.

For the customer’s request we provide official calibration.